1500W? At 12V that's 125A - That is fucking dangerous! Most sockets are rated at 20A. Most inverters that are >300W use crocodile clips, or preferably screw-down terminal rings. The cable looks way too thin too. That's a fire waiting to happen....

you are viewing a single comment's thread
view the rest of the comments
[–] jared@mander.xyz 17 points 2 weeks ago (3 children)

Ah, I'm sure the undersized copper coated aluminum wire will be fine, just fine.

[–] PhilipTheBucket@quokk.au 8 points 2 weeks ago (1 children)

I looked it up, and the recommended cable size for carrying that voltage and amperage is practically the size of the adapter part lol

[–] TimLovesTech@badatbeing.social 9 points 2 weeks ago

In the US you would need #2 [AWG] gauge wire to handle 125amps safely, and that's just handling the current, nothing to do with proper grounding or anything.

Also just for reference, many older homes in the US would only have 100 amp service from the pole, meaning this thing is pushing more amps than a whole house potentially.